Water - cooled module |
W050DZY |
|
||||||||||||
|
60 Hz Part Load
Data - English Units - Refrigerant HFC-134a |
||||||||||||||
|
Water Leaving
Chiller °F |
40 |
41 |
42 |
43 |
44 |
45 |
46 |
47 |
48 |
49 |
50 |
|||
|
|
||||||||||||||
|
Water Entering |
100%
LOAD |
|||||||||||||
|
85 |
Tons |
|
|
28.7 |
29.4 |
30.0 |
30.7 |
31.4 |
32.1 |
32.8 |
33.5 |
34.3 |
35.0 |
35.8 |
|
|
Btuh |
344,867 |
352,658 |
360,583 |
368,645 |
376,844 |
385,182 |
393,662 |
402,285 |
411,052 |
419,965 |
429,026 |
||
|
|
THR |
434,479 |
442,425 |
450,491 |
458,678 |
466,988 |
475,420 |
483,976 |
492,656 |
501,463 |
510,395 |
519,456 |
||
|
|
W |
26,241 |
26,286 |
26,327 |
26,364 |
26,396 |
26,424 |
26,446 |
26,463 |
26,475 |
26,481 |
26,480 |
||
|
|
kW/ton |
0.91 |
0.89 |
0.88 |
0.86 |
0.84 |
0.82 |
0.81 |
0.79 |
0.77 |
0.76 |
0.74 |
||
|
|
EER |
13.14 |
13.42 |
13.70 |
13.98 |
14.28 |
14.58 |
14.89 |
15.20 |
15.53 |
15.86 |
16.20 |
||
|
|
COP |
3.85 |
3.93 |
4.01 |
4.09 |
4.18 |
4.27 |
4.36 |
4.45 |
4.55 |
4.64 |
4.74 |
||
|
|
||||||||||||||
|
|
75%
LOAD |
|||||||||||||
|
75 |
Tons |
|
|
22.7 |
23.2 |
23.7 |
24.3 |
24.8 |
25.4 |
25.9 |
26.5 |
27.1 |
27.6 |
28.2 |
|
|
Btuh |
272,523 |
278,665 |
284,912 |
291,265 |
297,724 |
304,292 |
310,970 |
317,758 |
324,659 |
331,672 |
338,801 |
||
|
|
THR |
331,918 |
338,040 |
344,251 |
350,551 |
356,942 |
363,424 |
369,998 |
376,664 |
383,422 |
390,275 |
397,222 |
||
|
|
W |
17,392 |
17,387 |
17,376 |
17,361 |
17,341 |
17,315 |
17,285 |
17,249 |
17,208 |
17,160 |
17,107 |
||
|
|
kW/ton |
0.77 |
0.75 |
0.73 |
0.72 |
0.70 |
0.68 |
0.67 |
0.65 |
0.64 |
0.62 |
0.61 |
||
|
|
EER |
15.67 |
16.03 |
16.40 |
16.78 |
17.17 |
17.57 |
17.99 |
18.42 |
18.87 |
19.33 |
19.80 |
||
|
|
COP |
4.59 |
4.69 |
4.80 |
4.91 |
5.03 |
5.15 |
5.27 |
5.39 |
5.52 |
5.66 |
5.80 |
||
|
|
||||||||||||||
|
|
50%
LOAD |
|||||||||||||
|
65 |
Tons |
|
|
15.9 |
16.3 |
16.6 |
17.0 |
17.4 |
17.8 |
18.2 |
18.6 |
19.0 |
19.4 |
19.8 |
|
|
Btuh |
191,073 |
195,370 |
199,739 |
204,181 |
208,696 |
213,287 |
217,953 |
222,696 |
227,515 |
232,413 |
237,390 |
||
|
|
THR |
224,784 |
228,940 |
233,154 |
237,428 |
241,761 |
246,154 |
250,608 |
255,122 |
259,697 |
264,335 |
269,034 |
||
|
|
W |
9,871 |
9,830 |
9,785 |
9,736 |
9,682 |
9,624 |
9,562 |
9,495 |
9,424 |
9,347 |
9,266 |
||
|
|
kW/ton |
0.62 |
0.60 |
0.59 |
0.57 |
0.56 |
0.54 |
0.53 |
0.51 |
0.50 |
0.48 |
0.47 |
||
|
|
EER |
19.36 |
19.87 |
20.41 |
20.97 |
21.55 |
22.16 |
22.79 |
23.45 |
24.14 |
24.86 |
25.62 |
||
|
|
COP |
5.67 |
5.82 |
5.98 |
6.14 |
6.31 |
6.49 |
6.67 |
6.87 |
7.07 |
7.28 |
7.50 |
||
|
|
||||||||||||||
|
|
25%
LOAD |
|||||||||||||
|
65 |
Tons |
|
|
8.0 |
8.1 |
8.3 |
8.5 |
8.7 |
8.9 |
9.1 |
9.3 |
9.5 |
9.7 |
9.9 |
|
|
Btuh |
95,536 |
97,685 |
99,869 |
102,090 |
104,348 |
106,643 |
108,977 |
111,348 |
113,758 |
116,207 |
118,695 |
||
|
|
THR |
112,392 |
114,470 |
116,577 |
118,714 |
120,881 |
123,077 |
125,304 |
127,561 |
129,849 |
132,167 |
134,517 |
||
|
|
W |
4,936 |
4,915 |
4,893 |
4,868 |
4,841 |
4,812 |
4,781 |
4,748 |
4,712 |
4,674 |
4,633 |
||
|
|
kW/ton |
0.62 |
0.60 |
0.59 |
0.57 |
0.56 |
0.54 |
0.53 |
0.51 |
0.50 |
0.48 |
0.47 |
||
|
|
EER |
19.36 |
19.87 |
20.41 |
20.97 |
21.55 |
22.16 |
22.79 |
23.45 |
24.14 |
24.86 |
25.62 |
||
|
|
COP |
5.67 |
5.82 |
5.98 |
6.14 |
6.31 |
6.49 |
6.67 |
6.87 |
7.07 |
7.28 |
7.50 |
||
|
EER
|
Kw/Ton
|
COP
|
||||||||||||||
| IPLV |
22.34
|
IPLV
|
0.54
|
IPLV
|
6.54
|
|||||||||||
| COP or EER at 100% |
15.60
|
kW/ton at 100%
|
0.77
|
COP or EER at
100%
|
4.57
|
|||||||||||
| COP or EER at 75% |
19.10
|
kW/ton at 75%
|
0.63
|
COP or EER at
75%
|
5.59
|
|||||||||||
| COP or EER at 50% |
24.85
|
kW/ton at 50%
|
0.48
|
COP or EER at
50%
|
7.28
|
|||||||||||
| COP or EER at 25% |
24.85
|
kW/ton at 25%
|
0.48
|
COP or EER at
25%
|
7.28
|
|||||||||||
| IPLV (Integrated Part Load Valve) | ||||||||||||||||
| EER ( Energy Efficiency Ratio) + Btuh / Total power input in Watts | ||||||||||||||||
| Power input to unit, including controls, in kW to the net refrigerating capacity in tons | ||||||||||||||||