| modular chiller home | equipment | manual | profile | get a quote | links | site map |
   
Water-cooled module
W020DZY
Table 1 - 60 Hz Performance Data - English Units - Refrigerant 134a
Water Leaving Chiller °F
40
41
42
43
44
45
46
47
48
49
50
a a a a
a
a
a
a
a
a
a
a
a
a
a
Water Entering Condenser °F
a
a
a
a
a
a
aa
AA
a
a
70
Tons a a

13.4

13.7

14.0

14.3

14.6

14.9

15.3

15.6

15.9

16.3

16.6

a Btuh a a

160345

164011

167735

171519

175363

179266

183230

187255

191340

195487

199695

a
W a a

9174

9188

9202

9216

9230

9243

9256

9269

9282

9294

9306

a
EER a a

17.5

17.9

18.2

18.6

19.0

19.4

19.8

20.2

20.6

21.0

21.5

a
THR a a

191673

195387

199160

202991

206882

210831

214840

218908

223037

227226

231477

a a a a
a
a
a
a
a
a
a
a
a
a
a
75
Tons a a

13.0

13.3

13.7

14.0

14.3

14.6

14.9

15.3

15.6

15.9

16.3

a Btuh a a

156588

160189

163849

167568

171345

175183

179080

183038

187056

191135

195275

a
W a a

9708

9720

9733

9745

9757

9769

9780

9791

9802

9813

9823

a
EER a a

16.1

16.5

16.8

17.2

17.6

17.9

18.3

18.7

19.1

19.5

19.9

a
THR a a

189740

193385

197087

200847

204666

208544

212480

216476

220531

224646

228822

a a a a
a
a
a
a
a
a
a
a
a
a
a
80
Tons a a

12.7

13.0

13.3

13.6

13.9

14.2

14.6

14.9

15.2

15.5

15.9

a Btuh a a

152648

156179

159768

163416

167123

170889

174715

178600

182546

186552

190619

a
W a a

10283

10295

10307

10318

10329

10339

10350

10360

10369

10378

10387

a
EER a a

14.8

15.2

15.5

15.8

16.2

16.5

16.9

17.2

17.6

18.0

18.4

a
THR a a

187764

191336

194965

198652

202396

206198

210059

213978

217957

221995

226092

a a a a
a
a
a
a
a
a
a
a
a
a
a
85
Tons a a

12.4

12.7

13.0

13.3

13.6

13.9

14.2

14.5

14.8

15.1

15.5

a Btuh a a

148547

152003

155517

159089

162720

166409

170157

173965

177833

181761

185750

a
W a a

10898

10910

10921

10932

10943

10953

10962

10972

10981

10989

10998

a
EER a a

13.6

13.9

14.2

14.6

14.9

15.2

15.5

15.9

16.2

16.5

16.9

a
THR a a

185765

189261

192813

196422

200088

203812

207594

211434

215333

219290

223307

a a a a
a
a
a
a
a
a
a
a
a
a
a
90
Tons a a

12.0

12.3

12.6

12.9

13.2

13.5

13.8

14.1

14.4

14.7

15.1

a Btuh a a

144308

147684

151117

154608

158157

161764

165431

169156

172941

176785

180690

a
W a a

11552

11564

11576

11587

11597

11608

11617

11627

11636

11644

11652

a
EER a a

12.5

12.8

13.1

13.3

13.6

13.9

14.2

14.5

14.9

15.2

15.5

a
THR a a

183760

187176

190648

194177

197762

201405

205104

208862

212677

216551

220483

a
a a a
a
a
a
a
a
a
a
a
a
a
a
95
Tons a a

11.7

11.9

12.2

12.5

12.8

13.1

13.4

13.7

14.0

14.3

14.6

a Btuh a a

139955

143245

146592

149997

153459

156979

160558

164195

167891

171647

175463

a
W a a

12244

12256

12269

12281

12292

12303

12313

12323

12333

12342

12350

a
EER a a

11.4

11.7

11.9

12.2

12.5

12.8

13.0

13.3

13.6

13.9

14.2

a
THR a a

181767

185101

188490

191935

195436

198993

202608

206279

210008

213795

217639

a
a a a
a
a
a
a
a
a
a
a
a
a
a
100
Tons a a

11.3

11.6

11.8

12.1

12.4

12.7

13.0

13.3

13.6

13.9

14.2

a Btuh a a

135511

138709

141965

145278

148648

152076

155561

159105

162708

166370

170091

a
W a a

12971

12985

12999

13012

13025

13037

13049

13060

13070

13081

13090

a
EER a a

10.4

10.7

10.9

11.2

11.4

11.7

11.9

12.2

12.4

12.7

13.0

a
THR a a

179805

183053

186355

189713

193127

196596

200122

203704

207344

211040

214794

 

IPLV (Integrated Part Load Valve)

EER (Energy Efficiency Ratio) + Btuh/Total power input in Watts

Power input to unit, including controls, in kW to the net refrigerating capacity in tons

 
Notes:aaaaaa
Rated in accordance with with ARI Standard 550/590-2003  (see grey above)
1.- Evaporator:
      Flow 9 gpm / ton.
      10°F (5.5°C) Evaporator temperature drop
      Fouling factor 0.0001 h - ft2 - °F/Btu
2. Condenser:Based on 120°F (48.8°C) Condensing temperture

3. MCA - Minimum Circuit Ampacit6y (125% of the compressor 1 RLA plus 100% of the compressor 2 RLA

4.RFS - Recommended dual element Fuse Size
5. RCB - Recommended Circuit Breaker

6. Power inputs W

7. Sea Level

8. - Interpolation between points is acceptable.

9. - Extrapolation is not acceptable.