MODEL TRAC- 20D AIR COOLED CONDENSER DUAL REFRIGERATION CIRCUIT
TOTAL
HEAT OF REJECTION: 323,451 btu, 161,725 btu per circuit.
DESIGN
CONDITIONS: 95 F ambient air, condensing at 120 F with a 25
F temperature difference.
THESE
ARE SOME OF OUR STANDARD BENEFITS.
-
2 YEAR PARTS WARRANTY ON THE WHOLE UNIT.
- DUAL
REFRIGERATION CIRCUITS
-
COPPER TUBES WITH ALUMINUM FINS.
- FABRICATED
FORM HEAVY GAUGE LONG LASTING GALVANIZED STEEL.
- QUIET
MULTI-BLADED HIGH EFFICIENCY PROPELLER FANS.
- WEATHER
RESISTANT FAN MOTORS WITH INTERNAL OVER HEAT PROTECTION IN EACH
WINDING.
CORROSION
RESISTANT HOUSING: All our models employ mill galvanized steel
fan sections and coil sides, "C" section side supports and legs
of heavy mill galvanized steel with all bolted construction.
HIGH
EFFICIENCY COIL: Copper tubes are mechanically expanded into
corrugated full collared aluminum fins spaced 10 fins per. Coils
are pressure tested under water with 400 psig dry air and are shipped
pressurized. On units with one to five fans 3/8" grooved copper
tubes are used, on the six fan unit ½" smooth bore copper tubes
is used.
A liquid
subcooling circuit is incorporated in all condensers and is designed
to subcool the liquid 15 F.
COMPUTERIZED
COIL CIRCUITING: Our computerized coil circuiting program is
designed to minimize the condenser refrigerant charge and maximize
subcooling. Every condenser is custom circuited to precisely meet
each chiller requirement.
UNIQUE
COIL DESIGN: The unique coil support system utilizes stainless
steel tubes to isolate refrigerant tubes from the unit. Coil support
is transferred from the fins to the stainless steel tubes and truncated
tube plates which ride freely in "C" channels. Tubes expand and
contract without interference, resulting in elimination of contact
and friction wear.
This
unique coil design not only reduces wear but reduces sound. Fan
and coil vibration is isolated from the cabinet, so it is not transmitted
to the condenser frame and building supports.
CONDENSER
FANS: Quiet multi-bladed propeller fans provide uniform air
distribution through the coil. Venturi fan orifices optimize efficiency.
Condenser is two fans wide (one for each circuit) and has two fans
in each row, for a total of four.
Individual
fan compartments allow for individual fan cycling while preventing
off-fan "windmilling". Fan compartments come complete with large
clean-out access doors.
FAN
MOTORS: Our 1/2 hp 850 rpm condenser motors are designed for
outdoors with ball bearings, inherent overheat protection in each
phase, shaft slingers, enclosure, hardware and lubrication for all
weather conditions.
WEATHER
RESISTANT CONTROL PANEL: Standard weather resistant enclosure
is mounted to the frame, control panel is compete with 120V control
voltage transformer, primary and secondary fuses, fan contactors,
fan cycling control thermostats, three-phase fuses for fan motors
and pre-wired to fan motors. All that is required is a signal from
the chiller that the compressor is operating and the condenser automatically
controls the head pressure.
HEAD
PRESSURE CONTROL: Minimum requirement for head pressure control
is fan cycling, the lowest operating temperature with fan cycling
depends on the number of fans in the row, the firs fan does nut
cycle, with two fans the lowest operating temperature will be 62
F (16.6 C). with three fans it is 56 F (13.3 C), four fans is 49
F (9.4 C), five fans is 40 F (4.4 C), six fans is 17 F (-8.3 C).
We
recommend that fan speed control of the first fan be used along
with fan cycling, this will allow the condenser to operate down
to 0 F (-17.7 C ) ambient during the winter months.
SIZE:
00"l x 00"w x 49"h.
WEIGHT:
0,000 lbs.
VOLTAGE:
230/460/575V, 3 phase, 60 hertz.
200/380V,
3 phase, 50 hertz.
WARRANTY:
2 YEAR parts warranty on the whole unit.
OPTIONS
(add):
Fan
speed control of the first for low ambient control of head pressure
down $ to 0 F (-17.7 C) ambient during the winter months.
Flooded
condenser with pressure control valves for low ambient control $
of head pressure down to -20 F (-28.8 C).
|