TANDEM
MODEL TAFC- 20 AIR COOLED DRY FLUID COOLER
TOTAL
HEAT OF REJECTION: 323,451 btu.
DESIGN
CONDITIONS: To cool 65 gpm of water to 105 F leaving temperature
with 95 F ambient air.
THESE
ARE SOME OF OUR STANDARD BENEFITS.
-
2 YEAR PARTS WARRANTY ON THE WHOLE UNIT.
-
COPPER TUBES WITH ALUMINUM FINS.
- FABRICATED
FORM HEAVY GAUGE LONG LASTING GALVANIZED STEEL.
- QUIET
MULTI-BLADED HIGH EFFICIENCY PROPELLER FANS.
- WEATHER
RESISTANT FAN MOTORS.
CORROSION
RESISTANT HOUSING: All our models employ mill galvanized steel
fan sections and coil sides, "C" section side supports and legs
of heavy mill galvanized steel with all bolted construction.
HIGH
EFFICIENCY COIL: Copper tubes are mechanically expanded into
corrugated full collared aluminum fins spaced 12 fins per. Coils
are pressure tested under water with 400 psig dry air and are shipped
pressurized. ½" smooth bore copper tubes are used.
COMPUTERIZED
COIL CIRCUITING: Our computerized coil circuiting program is
designed to minimize the fluid cooler pressure drop and maximize
efficiency. Every fluid cooler is custom circuited to precisely
meet each chiller requirement.
UNIQUE
COIL DESIGN: The unique coil support system utilizes stainless
steel tubes to isolate refrigerant tubes from the unit. Coil support
is transferred from the fins to the stainless steel tubes and truncated
tube plates which ride freely in "C" channels. Tubes expand and
contract without interference, resulting in elimination of contact
and friction wear.
This
unique coil design not only reduces wear but reduces sound. Fan
and coil vibration is isolated from the cabinet, so it is not transmitted
to the condenser frame and building supports.
FANS:
Quiet multi-bladed propeller fans provide uniform air distribution
through the coil. Venturi fan orifices optimize efficiency.
Individual
fan compartments allow for individual fan cycling while preventing
off-fan "windmilling". Fan compartments come complete with large
clean-out access doors.
FAN
MOTORS: Our dry cooler fan motors are designed for outdoor operation
with ball bearings, inherent overheat protection in each phase,
shaft slingers, enclosure, hardware and lubrication for all weather
conditions.
WEATHER
RESISTANT CONTROL PANEL: Standard weather resistant enclosure
is mounted to the frame. The control panel compete with 120V control
voltage transformer, primary and secondary fuses, fan contactors,
fan cycling control thermostats, three-phase fuses for fan motors
and pre-wired to fan motors. All that is required is a signal from
the chiller that the compressor is operating, and the fluid cooler
automatically controls the leaving water temperature.
FLUID
TEMPERATURE CONTROL: Fluid temperature control is maintained
by cycling the fans on the leaving fluid temperature, aquastat thermostats
are used to cycle each fan maintaining constant leaving water temperature.
SIZE:
00"l x 00"w x 49"h.
WEIGHT:
0,000 lbs.
VOLTAGE:
230/460/575V, 3 phase, 60 hertz.
200/380V,
3 phase, 50 hertz.
WARRANTY:
2 YEAR parts warranty on the whole unit.
ALTERNATE
FLUID COOLER:
Fluid
cooler designed for 45% ethylene glycol operation with increased
flow to maintain capacity, required for low ambient winter operation
to prevent freezing of cooling fluid.
|